PowerFlex® 6000 Medium Voltage Variable Frequency Drive
Commissioning Manual
Publication 6000-IN007A-EN-P
Commissioning Manual
Vista de pagina 0
1 2 3 4 5 6 ... 97 98

Indice de contenidos

Pagina 1 - Commissioning Manual

PowerFlex® 6000 Medium Voltage Variable Frequency Drive Commissioning ManualPublication 6000-IN007A-EN-PCommissioning Manual

Pagina 2 - Important User Information

10 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014PrefaceNotes:

Pagina 3 - Table of Contents

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 11Chapter 1IntroductionOverviewInformation contained in this chapter will assist in co

Pagina 4

12 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 1 IntroductionProcess FlowchartsDocumentation and Application ReviewReview a

Pagina 5

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 13Introduction Chapter 1• PLC Program: The PLC I/O processes control signals within th

Pagina 6

14 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 1 IntroductionOn-site Verification of Electrical System One-line DiagramOnce

Pagina 7 - Table 1 - Electrical Drawings

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 15Chapter 2Preparation and InspectionGather Required Tools and Test EquipmentHand Tool

Pagina 8

16 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionLockout and tagout the input circuit breaker bef

Pagina 9 - Additional Resources

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 17Preparation and Inspection Chapter 2Functional AssessmentAfter the components are vi

Pagina 10

18 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionTable 3 - Inspect Drive Components ChecklistBypa

Pagina 11 - Introduction

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 19Preparation and Inspection Chapter 2Table 4 - Functional Assessment ChecklistBypass

Pagina 12 - Application Review

Important User InformationRead this document and the documents listed in the additional resources section about installation, configuration, and opera

Pagina 13 - Review Drive Application

20 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionInterconnection ReviewThe interconnection checkl

Pagina 14 - Chapter 1 Introduction

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 21Preparation and Inspection Chapter 2Installation ReviewPrior to commencing the commi

Pagina 15 - Preparation and Inspection

22 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionElectrical Installation InspectionPower CablingT

Pagina 16 - Inspect Drive Components

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 23Preparation and Inspection Chapter 2Incoming Line and Outgoing Motor cables must be

Pagina 17 - Functional Assessment

24 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and Inspection2. Disconnect four 380V AC cables (a, b, c, and

Pagina 18

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 25Preparation and Inspection Chapter 25. Switch the miniature circuit breakers in the

Pagina 19

26 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and Inspection8. Disconnect the control cable of HECS.Figure 7

Pagina 20 - Interconnection Review

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 27Preparation and Inspection Chapter 210. Remove the Analog Interface board and discon

Pagina 21 - Installation Review

28 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and Inspection5. Disconnect the Insulation Meter and jumpers i

Pagina 22 - Power Cabling

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 29Preparation and Inspection Chapter 2Final Steps before Equipment is Ready for Energi

Pagina 23 - Drive Megger Check

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 3Table of ContentsPrefaceIntroduction. . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 24

30 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionNotes:

Pagina 25 - Figure 5 - Control Switches

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 31Chapter 3CommissioningIntroductionA number of activities are required before the Con

Pagina 26 - Figure 8 - Back of HMI

32 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningControl System Check SetupSimulate Closed Input Circuit Break

Pagina 27 - Connect the Insulation Meter

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 33Commissioning Chapter 3Figure 14 - LV Control CabinetFigure 15 - LV Panel in the Iso

Pagina 28

34 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningFigure 16 - AC/DC Power SuppliesTable 8 - Energize Control Ci

Pagina 29 - Energization

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 35Commissioning Chapter 3Control System CheckVerify Factory Default SettingsConfirm La

Pagina 30

36 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press and confirm the Bypass Configuration matches one o

Pagina 31 - Commissioning

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 37Commissioning Chapter 3The Select Local Control? dialog box appears.5. Select to c

Pagina 32 - Control System Check Setup

38 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningThe Setup Login dialog box appears. Press .3. Enter the User

Pagina 33

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 39Commissioning Chapter 3For the simulation tests, you only need to change two paramet

Pagina 34

4 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Table of ContentsVerify E-Stop Functionality . . . . . . . . . . . . . . . . . . . .

Pagina 35 - Control System Check

40 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press “0” on the keypad dialog and press .Parameter 007 w

Pagina 36 - , press

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 41Commissioning Chapter 3Verify Operation of Frequency StepsThere are two parts to thi

Pagina 37 - Access Setup Settings

42 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press , and press in the Start Drive? dialog box to con

Pagina 38 - Set P Parameters

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 43Commissioning Chapter 35. Press and press in the Decel Speed by Step? dialog box

Pagina 39 - Commissioning Chapter 3

44 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning2. Press to accept and begin the simulation.Actual Frequenc

Pagina 40 - Chapter 3 Commissioning

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 45Commissioning Chapter 3Simulate Warnings and FaultsThis section describes how to sim

Pagina 41 - Increase Frequency by Step

46 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press to view alarm record..4. Remove the jumper wires t

Pagina 42

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 47Commissioning Chapter 36. Press , and press to confirm the operation in the Reset

Pagina 43

48 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press to confirm the Transformer Cabinet Main Cooling Fa

Pagina 44

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 49Commissioning Chapter 33. Press and confirm the Power Module Cabinet Fan Fault.4.

Pagina 45 - Simulate Warnings and Faults

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 5Table of ContentsSpeed Reference Functions. . . . . . . . . . . . . . . . . . . . . .

Pagina 46

50 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning5. Press to return to the Main Interface Screen. 6. Press

Pagina 47

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 51Commissioning Chapter 36. Press to remove the fault. Press to confirm operation

Pagina 48

52 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning6. Under Control Owner Selection, press .7. Select to conf

Pagina 49

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 53Commissioning Chapter 32. Open the Bypass cabinet door, and close QS2 and QS3.Verify

Pagina 50 - Verify E-Stop Functionality

54 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningBypass Isolation Switches1. Press from the Main Interface s

Pagina 51

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 55Commissioning Chapter 33. Close the customer-supplied input circuit breaker by insta

Pagina 52 - (Manual Bypass)

56 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning2. Close the customer-supplied input circuit breaker by insta

Pagina 53

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 57Commissioning Chapter 3Verify the input and output drive contactors are closed.4. Pr

Pagina 54 - Bypass Isolation Switches

58 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning5. Verify the input and output drive contactors are closed.By

Pagina 55 - (Automatic Bypass)

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 59Commissioning Chapter 32. Press under Contactor Operation, and press to confirm..

Pagina 56

6 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Table of ContentsNotes:

Pagina 57 - , and press

60 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press under Contactor Operation, and press to confirm..

Pagina 58 - Bypass Contactors

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 61Commissioning Chapter 3Verify Operation of DCS Input and Output SignalsFigure 17 - S

Pagina 59

62 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningWhen the two terminals specified are shorted, verify the resu

Pagina 60

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 63Commissioning Chapter 3Press to enter password details. Press when finished.3. P

Pagina 61 - Table 10 - 4-20 mA

64 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningSet Date and Time ZoneTo access the Date and Time Zone settin

Pagina 62 - Restore P Parameter Settings

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 65Commissioning Chapter 3Change Time/Date/Regional Settings1. In Windows ME, press Ter

Pagina 63

66 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningNotes:

Pagina 64 - Set Date and Time Zone

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 67Chapter 4No-load TestIntroductionNo-load TestThe No-load Test consists of the follow

Pagina 65

68 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestEnergize Drive Control CircuitThe “Energize Control Circuit” p

Pagina 66

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 69No-load Test Chapter 4P091 Skip Frequency 1 Upper Limit 0 ON 0 75 R&DP092 Skip F

Pagina 67 - No-load Test

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 7PrefaceIntroductionThis document provides procedural information for commissioning Po

Pagina 68 - Configure P and T Parameters

70 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestThere are no specific T parameters to modify when commissionin

Pagina 69 - 0 ON -100 199.99 R&D

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 71No-load Test Chapter 4Parameters T11...T13To change Parameter T11:1. Press the T11 P

Pagina 70 - (2) With Remote DCS only

72 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load Test2. In the Switch Method Selection dialog, press or . 3. If

Pagina 71 - Parameters T11...T13

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 73No-load Test Chapter 4Change Parameter T12:1. Press the T12 Parameter input field.2.

Pagina 72 - Chapter 4 No-load Test

74 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestChange Parameter T13:1. Press the T13 Parameter input field.2.

Pagina 73 - 3. Press to accept

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 75No-load Test Chapter 4Close Isolation Switches in Bypass Cabinet1. Manual bypass (se

Pagina 74

76 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestOperate Motor by HMI1. From the Main Interface Screen, press t

Pagina 75 - Check Cooling Fan Operation

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 77No-load Test Chapter 43. Press , and press in the Start Drive? dialog box to conf

Pagina 76 - Operate Motor by HMI

78 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load Test5. From the Main Interface Screen, press the Set Frequency: in

Pagina 77 - No-load Test Chapter 4

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 79No-load Test Chapter 47. Press , and press in the Start Drive? dialog box to conf

Pagina 78 - Press to confirm

8 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014PrefaceIf the drawings require changes to suit the installation and application of th

Pagina 79

80 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load Test13. Switch on the customer-supplied control power, and push th

Pagina 80 - Load Test of Drive System

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 81Appendix ATorque RequirementsTorque RequirementsProper tightening torque must be use

Pagina 81 - Torque Requirements

82 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix A Torque RequirementsNotes:

Pagina 82

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 83Appendix BSingle Line DiagramsFigure 18 - PowerFlex 6000 without BypassQFInput Circu

Pagina 83 - Single Line Diagrams

84 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix B Single Line DiagramsFigure 19 - 6012M Automatic Bypass Version 1 (without

Pagina 84

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 85Single Line Diagrams Appendix BFigure 20 - 6012M Automatic Bypass Version 2 (with Is

Pagina 85

86 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix B Single Line DiagramsFigure 21 - 6012M Manual BypassQFInput Circuit Breake

Pagina 86

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 87Appendix CSpecial Function Parameter SettingsOverviewTable 12 on page 68 outlines sp

Pagina 87 - System Setting Functions

88 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSwitch Control SourcesRelevant paramet

Pagina 88 - Motor Parameter Setting

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 89Special Function Parameter Settings Appendix CAnalog Output Display Parameter Settin

Pagina 89 - Restore Factory Setting

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 9PrefaceGeneral PrecautionsAdditional ResourcesThese documents contain additional info

Pagina 90 - Speed Command Functions

90 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSpeed Command FunctionsSet Frequency C

Pagina 91 - Frequency Skip

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 91Special Function Parameter Settings Appendix CFrequency Amplitude LimitRelevant para

Pagina 92 - Speed Reference Functions

92 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSpeed Reference FunctionsV/F Curve Set

Pagina 93 - Flying Start Function

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 93Special Function Parameter Settings Appendix CAnalog InputRelevant parameter: P205,

Pagina 94 - Restart the Drive

94 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSome parameters must be changed based

Pagina 95

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 95IndexAAnalog Input 93CCabinet PlatesPre-Commissioning Sealing 29Commissioning 31Cont

Pagina 96

96 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014IndexMechanical Inspection 21Interconnection Review 20Checklist 20Software 15Test Eq

Pagina 98 - Documentation Feedback

Publication 6000-IN007A-EN-P - October 2014 - Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in Canada.Rockwell Automati