Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 65
Commissioning Chapter 3
Change Time/Date/Regional Settings
1. In Windows ME, press Ter m in a l S e t t i n g s [ F 4 ] .
2. Press the Down Arrow to choose Time/Date/Regional Settings, and press
Enter.
3. Choose Time zone and press Enter.
4. Scroll up or down and select the desired time zone.
a. Press Daylight Savings [F1]
b. Select the Yes radio button, and press Close [F8].
5. Press OK [F7].
6. Choose Date and press Enter.
a. Press Ye a r [ F 1 ] , Month [F2], and Day [F3] to set the correct date.
b. Press OK [F7].
7. Choose Time and press Enter.
a. Press Hour [F1], Minute [F2], and Seconds [F3] to set the correct
time.
b. Press OK [F7].
8. Press Close [F8] twice, Reset [F7], and Yes [ F 7 ] to restart the HMI.
9. Select language and bypass mode in the System Parameters Settings
interface.
10. Press to accept and proceed to the Main Interface Screen.
Verify the date and time is updated under Version Info.
IMPORTANT
Enter the Time Zone settings before changing the date and time.