Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 45
Commissioning Chapter 3
Simulate Warnings and Faults
This section describes how to simulate warnings and faults, and how to clear or
reset the alarm. Warning codes begin with a W prefix, and fault codes begin with
a F prefix.
The Set Frequency: field will already have 50 Hz shown from the previous
exercise in the Set Freq: dialog box.
1. Press , and press in the Start Drive? dialog box.
Simulate the Transformer Overtemperature Warning
1. Open the LV door of the Isolation Transformer cabinet.
2. Using a jumper wire, connect terminal blocks 401 and 419 on the
transformer protection relay.
Alarm Self-clearing Requires Reset
Transformer Overtemperature Warning YES
Transformer Overtemperature Trip YES
Transformer Cabinet Main Cooling Fan Fault YES
Power Module Cabinet Main Cooling Fan Fault YES
Cabinet Door Open Warning
Left Isolation Transformer Cabinet Door
Right Isolation Transformer Cabinet Door
Left Power Module/LV Cabinet Door
Right Power Module/LV Cabinet Door
Bypass Cabinet Door (if applicable)
YES