Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 31
Chapter 3
Commissioning
Introduction
A number of activities are required before the Control System Check can be
performed.
The complete Control System Check requires the following procedures to be
performed.
ATTENTION: The Control System Check requires LV Control power only. The
Input Circuit Breaker must remain locked out and tagged out for this procedure.
Procedure Page
Simulate Closed Input Circuit Breaker
32
Energize Control Circuit 32
Procedure Page
Verify Factory Default Settings 35
Set P Parameters to Enable Testing 37
Verify Operation of Frequency Steps 41
Verify Operation to Set Frequency 43
Simulate Warnings and Faults 43
Verify E-Stop Functionality 50
Verify Switching from Local Control to Remote Control 51
Verify Operation of Input/Output and Bypass Isolation Switches (Manual Bypass)
(1)
(1) Only required if a bypass configuration is supplied.
52
Verify Operation of Input/Output and Bypass Contactors (Automatic Bypass)
(1)
55
Verify Operation of DCS Input and Output Signals 61
Restore P Parameter Settings 62