50 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014
Chapter 3 Commissioning
5. Press to return to the Main Interface Screen.
6. Press to remove the fault. Press to confirm
operation in the Reset Drive? dialog.
Verify E-Stop Functionality
1. Press on the Main Interface Screen to start the drive.
2. Push the E-stop button on the front of the LV Control cabinet.
3. Press and confirm the E-stop Trip fault.
4. Twist to pull out the E-stop button on the front of the LV Control cabinet.
5. Press to return to the Main Interface Screen.