Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 71
No-load Test Chapter 4
Parameters T11...T13
To change Parameter T11:
1. Press the T11 Parameter input field.
T08 Remote Frequency Command Selection
1: Analog
2: 4-Step Speed
4: Communication Port
1 ON 1 4 Setup Confirm P262=1
If T8=1, then the analog quantity 4...20 mA from Remote,
4 mA corresponds to 0 Hz, 20 mA corresponds to the rated
frequency.
If T8=2, use T13 to set step speed
If T8=4, communication mode with remote
T09 Frequency Step For Accel or Decel 1 ON 1 Rated
Frequency
Setup Changes the step frequency when Accel or Decel is pressed
T10 Exit Config Environment Password 555 OFF Setup This function will not work if the drive is running.
T11 Automatic Bypass-To-Drive or
Drive-To-Bypass Selection
Setup
T12 PID Parameter Settings Setup
P 0.01 ON 0 32767
I 0.01 ON 0 32767
D 0 ON 0 32767
D Gain 0 ON 0 32767
T13 4-Step Variable Speed
(available only when T8=2)
Setup
Speed 1 10 ON 0 Rated
Frequency
Speed 2 20 ON 0 Rated
Frequency
Speed 3 30 ON 0 Rated
Frequency
Speed 4 40 ON 0 Rated
Frequency
(1) ON: Can be modified at any time. OFF: Drive must be off to modify.
T
Parameter
Description Default Modify
Root
(1)
Min.
Value
Max.
Value
Login
Level
Instruction