Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 69
No-load Test Chapter 4
P091 Skip Frequency 1 Upper Limit 0 ON 0 75 R&D
P092 Skip Frequency 2 Lower Limit 0 ON 0 75 R&D
P093 Skip Frequency 2 Upper Limit 0 ON 0 75 R&D
P113 Flying Start-Initial Output Voltage
Percentage (%)
5ON0100R&D
P114 Flying Start-Current Comparison Delay For
Motor Speed Search (ms)
1000 ON 0 5000 R&D
P115 Flying Start-Current Threshold For Successful
Motor Speed Search
5ON0100R&D
P198 HECS Rated Current (A) 0 ON 0 5000 Setup Set value according to the Electrical Drawings
P199 Motor Rated Current (A) 0 ON 0 5000 Setup Set value according to the customer motor nameplate data
P205 Motor Uab Voltage Scaling Factor Correction 199.99 ON 0 199.99 R&D
P206 Motor Uac Voltage Scaling Factor Correction 199.99 ON 0 199.99 R&D
P213 Output Short-Circuit Fault Threshold 180 ON 0 199.99 Setup
P216 High-Frequency Output Over Current
Threshold
120 ON 0 199.99 Setup
P224 Output Voltage Deviation Fault Threshold 80 ON 0 199.99 Setup Set to 120 for Control System Check. Set to 80 afterwards
P252 Motor In Stopping Condition Threshold 1 ON 0 100 R&D
P253 Motor Coast Stop Time 10 ON 0 10000 R&D
P259 Frequency Command Analog Offset 0 ON -100 199.99 R&D
P260 Frequency Command Analog Scaling Factor 100 ON 0 199.99 Setup
P262 Frequency Command Source Selection
0: Digital
1: Analog
0OFF01Setup
P335 Analog Output #1 Scaling Factor 100 ON 0 199.99 Setup DCS display the output voltage proportion coefficient and can be
changed as the customer operation request from 0...200%
(2)
P339 Analog Output #2 Scaling Factor 100 ON 0 199.99 Setup DCS display the output current proportion coefficient and can be
changed as the customer operation request from 0...200%
(2)
P352 Rated Frequency HMI Display Integer Part 50 ON 0 75 Setup
P355 Motor Voltage HMI Display Integer Part 10000 ON 0 16384 Setup Local display voltage correction coefficient, the value must be
done according to the rating of the inverter output voltage
setting.
For example: if the output is 3 kV, then set P355 = 3000
P358 Actual Frequency HMI Display Integer Part 50 ON 0 75 Setup
P361 Motor Current HMI Display Integer Part 0 ON 0 5000 Setup Normally P361 = P199
P399 Deceleration Time (s) 300 ON 0 3276 Setup Default value is 300 s. Set according to customer specification
The time from 50...0 Hz after stopping the motor
P401 Acceleration Time (s) 200 ON 0 3276 Setup Default value is 200 s. Set according to customer specification
The time from 0...50 Hz after starting the motor
P413 Frequency Command Lower Limit 0 ON -16384 16384 R&D
P414 Frequency Command Deadband Upper Limit 0.49 ON 0 100 R&D
P415 Frequency Command Upper Limit 16384 ON -16384 16384 R&D
Table 12 - Setup and R&D Parameters (Continued)
P
Parameter
Description Default Modify
Root
(1)
Min.
Value
Max.
Value
Login
Level
Instruction