QUICK STARTARMORSTART® DISTRIBUTED MOTOR CONTROLLERGetting StartedBULLETIN 280D/281DIntroduction This guide provides the basic information required to
10 Publication 280D-QS001D-EN-P - July 2006ArmorStart with ArmorConnect ConnectivityInstalling ArmorConnect Power Media using Cord GripsContro
Publication 280D-QS001D-EN-P - July 2006 11ArmorConnect Cable RatingsThe ArmorConnect Power Media cables are rated per UL Type TC 600V 90 °C Dr
12 Publication 280D-QS001D-EN-P - July 2006Group Motor Installations for USA and Canada MarketsThe ArmorStart Distributed Motor controllers are
Publication 280D-QS001D-EN-P - July 2006 13maintenance while energized. In lieu of this service, the ArmorStart is meant to be unplugged and re
14 Publication 280D-QS001D-EN-P - July 2006LED Status Indication The LED Status Indication provides 4 status LEDs and a Reset button. The LEDs
Publication 280D-QS001D-EN-P - July 2006 15Node Commissioning using HardwareThe ArmorStart is shipped with the hardware rotary switches set to
16 Publication 280D-QS001D-EN-P - July 2006required, the information below can be used to map a device based on the default configuration.Table
Publication 280D-QS001D-EN-P - July 2006 17Use the software to access the device parameters screen. By default the motor FLA is set to the mini
18 Publication 280D-QS001D-EN-P - July 2006Quick Reference TroubleshootingThere are four LEDs on the front of the ArmorStart that can provide a
Publication 280D-QS001D-EN-P - July 2006 19Fault LED indications for Bulletin 280D and 281D ArmorStart Distributed Motor ControllersTable 8 Con
2 Publication 280D-QS001D-EN-P - July 2006Installation The ArmorStart Distributed Motor Controller is convection cooled. Operating temperature
20 Publication 280D-QS001D-EN-P - July 2006Bulletin 280/281 ParametersTable 9 Starter Display and Parameter SettingsTable 10 FLA Setting Ranges
Publication 280D-QS001D-EN-P - July 2006 21Figure 11 Bulletin 280/281 ArmorStartFigure 12 Bulletin 280/281 ArmorStart with ArmorConnectLED Stat
22 Publication 280D-QS001D-EN-P - July 2006Table 11 DeviceNet Media ➊ ➊See publication M116-CA001A-EN-P for complete cable selection informatio
Publication 280D-QS001D-EN-P - July 2006 23Table 12 Sensor Media ➊ ➊See Publication M116-CA001A-EN-P for complete cable selection information.➋
Publication 280D-QS001D-EN-P — July 2006 41053-384-01 (1)Superecedes Publication 280D-QS001C-EN-P — September 2005 Copyright ©2006 Rockwell Automation
Publication 280D-QS001D-EN-P - July 2006 3Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturin
4 Publication 280D-QS001D-EN-P - July 2006Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturin
Publication 280D-QS001D-EN-P - July 2006 5Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturin
6 Publication 280D-QS001D-EN-P - July 2006Wiring Power, Control, Safety Monitor Inputs, and Ground Wiring Table 1 provides the power, control,
Publication 280D-QS001D-EN-P - July 2006 7Table 2 Power, Control, Safety Monitor, and Ground Terminal Designations➊ Only available with the Saf
8 Publication 280D-QS001D-EN-P - July 2006ArmorConnect Power Media DescriptionThe ArmorStart Power Media offers both three-phase and control po
Publication 280D-QS001D-EN-P - July 2006 9Figure 7 Control Power Media System Overview➏ Control Power Media Patchcords - PatchCord cable with