Rockwell-automation 4100 REC Resolver to Encoder Converter Installatio Manual de usuario Pagina 16

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 50
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 15
Publication 999-126 - February 1996
Installation & Hook-Up 11
Figure 2.1
Mounting and Grounding Diagram
Mount the REC next to a 1394 GMC system or an S Class Compact
motion controller on a metal enclosure panel using two 1/4 -20 or M6
bolts. Refer to the Mechanical Specifications in the Overview chapter
of this manual for mounting dimensions. Figures 2.2 and 2.3 in this
chapter show where to mount the REC.
#10 AWG to
Ground Bus
Ground
Lug
Internal Star Washers
REC Mounting Tab
Size 1/4 - 20 or M6
Hardware
Tapped Hole
(Minimum of 3 Threads)
Metal Panel
(Must be connected to
earth ground.)
Scrape paint off panel to insure
electrical connection between
chassis and grounded metal plate.
!
ATTENTION:
To avoid a shock hazard, remove all
power to the system panel before mounting the REC.
ATTENTION:
The 1394 contains stored energy
devices. To avoid the hazard of electrical shock, verify
that all voltages are zero (0.00) before proceeding.
Vista de pagina 15