For DCS 5000, AutoMax, or Distributed Power DĆC Drive
systems, use the DCS 5000 or AutoMax Programming
Executive software I/O Monitor function, respectively. Test
output channels by writing a value between 0 and 4095 to
those channels and using a voltmeter to verify that the
signal on the terminal points (0 to 10V) is proportional. To
test input channels, verify that the input signal in the
channel (0 to 10V) is proportional to a voltmeter reading
at the terminal points.