Rockwell-automation 61C542 Voltage Input module Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 68
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
2Ć4
modules can read all locations within the module's slot address, but
can only write to registers 23 through 31.
The module performs a full complement of powerĆup diagnostics
which must execute successfully before the module enters the run
mode. Any diagnostic test failure results in a module shutdown.
UserĆSupplied
Voltage
Transmitter
(SingleĆ
Ended)
UserĆSupplied
Voltage
Transmitter
(DifferĆ
ential)
Terminal Board and
Cable Assembly
(M/N 61C547/61C548)
37ĆPin
DĆShell
Connectors
*Analog
Common
A/D
+
-
M
U
X
0.1F
0.1F
0.1F
0.1F
220K
220K
220K
220K
10m
10m
10m
+15V
+15V
+15V
1A
2A
3B
3A
14B
15B
A
V
IN
+
Analog
Common
V
IN
+
V
IN
-
 (1)ăAll A" terminals ( A-15A) are tied to the analog common bus.
(2)ăAll analog inputs must be within 10V of analog common for proper operation.
Voltage Input Module
(M/N 61C542)
Figure 2.2 Ć Typical Voltage Input Channel
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 67 68

Comentarios a estos manuales

Sin comentarios