4-8 Configuring the Encoder Using RSNetWorx for DeviceNet
Setting Parameters to
Default Values
In order to reset the parameters to the factory default values, the
service Reset (05
hex
) of the encoder object is used. This is done in the
Class Instance Editor. Select the service Reset (05
hex
) of the object
2F
hex
(encoder object), Instance 1, with the ‘Send the attribute ID’
box unchecked. Finish by clicking on the Execute button.