B-7 DeviceNet Information
Publication 855T-UM001C-EN-P May 2005
The data for off_delay is time in microseconds, valid values: 0, 2000, 4000, 8000, 16000.
The data for on_delay is time in microseconds, valid values: 0, 2000, 4000, 8000, 16000.
Disable Autobaud: 0 = Enabled, 1 = Disabled
Fault State: 0 = Reset Outputs, 1 = Hold Last State
Idle State: 0 = Reset Outputs, 1 = Hold Last State
Common Services
Table B.11 Assembly Object, Instance 104 Attributes
Attribute Access Name Type Value
3Get/SetData
Off_delay
On_delay
Autobaud
DOG_Fault_State
DOG_Idle_State
STRUCT of:
UINT
UINT
BOOL
BOOL
BOOL
Table B.12
Service Code Class Instance Service Name
14 (0x0E) Yes Yes Get_Attribute_Single
16 (0x10) No Yes Set_Attribute_Single