937CU-AIHLP-DC1 Installation Instructions HART Loop Converter
1 Removable terminals, blue2LC display Display for showingthe measured valuesthe current output valuesthe fault messagesthe parameterization mode3
Number of terminal blocks max. 10Dimension drawing with screw terminalsWhen using screw terminals with test sockets the device is 124 mm (4.9 in) in
DIN Mounting RailThe devices are mounted on a 35 mm DIN mounting rail according to EN 60715.Example: DIN mounting rail(35 mm x 15 mm)Power RailTo redu
Power Rail is available in two sizes:Power Rail 937A-PR08 and 937A-PR20 Three leads:• two conductors for power•one conductor for collective error mes
MountingMounting the Isolated BarrierSnap the device onto the DIN mounting rail in a vertical downward movement. See figure below.Mounting the Termina
ConnectionThe removable terminal blocks simplify connection and control cabinet construction significantly. These terminal blocks offer adequate space
+1+2+-3-45250 Ω6ERR 24 V DCPower RailHART+-mA+-Zone 0, 1, 2Div. 1, 2HARTHARTBul. 937C HART Loop Converter Installation Instructions14
Connection The following connections are available:Terminals 10 ... 12: output I (relay 1 (change-over contact))Terminals 16 ... 18: output II (rela
Connecting a HART Handheld to the Field DeviceYou have two options for connecting a HART handheld to the field device:Connection to terminals 22/24 o
Polling Mode (command and answer)The isolated barrier deactivates the burst configuration of the field device. The isolated barrier performs the field
ConfigurationConfiguring the DeviceConfigure the device using the buttons on the front side. Use the ,, ESC, and OK buttons for navigation. The fol
Parameterization ModeAfter being switched on, the device is in display mode. If you have password protection enabled, you must enter the password ever
Password ProtectionYou can activate password protection to protect parameterization from unauthorized changes. Ifpassword protection is enabled, you
Bul. 937C HART Loop Converter Installation InstructionsEntering NumbersAt the lowest menu level of the Parameter menu, you have the option of selectin
Bul. 937C HART Loop Converter Installation Instructions Entering Floating Point FiguresAt the lowest menu level of the Parameter menu, you have the op
Bul. 937C HART Loop Converter Installation InstructionsEntering a Numerical Value1. Select the parameter for which you want to enter the numerical val
Bul. 937C HART Loop Converter Installation InstructionsUnitAt the lowest menu level of the Unit menu, you have the option of selecting the unit type f
Bul. 937C HART Loop Converter Installation InstructionsChanging the Custom Tag of HART Variables1. Select the HART variable for which you would like t
Bul. 937C HART Loop Converter Installation InstructionsHARTcomThe HARTcom menu offers the option of specifying the method for communication between de
Bul. 937C HART Loop Converter Installation InstructionsSelecting a ModeThe device functions as primary or secondary HART master according to
1Bul. 937C HART Loop Converter Installation InstructionsSymbols UsedThis symbol warns of possible danger. Failure to heed this warning may result in p
Bul. 937C HART Loop Converter Installation InstructionsEditing device data: Input Defining ShortAddressThe defined short address is needed for identif
Bul. 937C HART Loop Converter Installation InstructionsIf the connection to the field device has been lost, the localization phase can be performed wi
Bul. 937C HART Loop Converter Installation InstructionsEditing device data: InputSelecting an AssignmentThe values of the selected HART variable (PV,
Bul. 937C HART Loop Converter Installation InstructionsEditing device data: InputDefining a CharacteristicThe choice of characteristic defines the lim
Bul. 937C HART Loop Converter Installation InstructionsExampleCharacteristic 4 - 20 NE43, start value 2 bar, end value 10 barThe type of fault current
Bul. 937C HART Loop Converter Installation InstructionsRelay Contact OutputsIn the Output menu, you have the option of defining relay contact outputs
Bul. 937C HART Loop Converter Installation InstructionsSelecting Relay Contact Output Menus1.Select the desired relay contact output using the or
Bul. 937C HART Loop Converter Installation InstructionsCalling up a Trip Value1.Select the Trip value menu with the or buttons.2. If the trip value
Bul. 937C HART Loop Converter Installation InstructionsSelecting an AssignmentThe values of the HART variables selected here (PV, SV, TV, QV) are moni
Bul. 937C HART Loop Converter Installation InstructionsYou can implement the following applications:Switching direction max, direction of operation a
2Bul. 937C HART Loop Converter Installation InstructionsSafety NotesThe HART Loop Converter must only be operated by trained personnel in accordance w
Bul. 937C HART Loop Converter Installation InstructionsDefining the Trip Point1. Enter the starting point as a floating point figure. For entering flo
Bul. 937C HART Loop Converter Installation InstructionsResponse delay has the following effects:When the value of the trip point is out of range (exc
Bul. 937C HART Loop Converter Installation InstructionsCalling up a Fault Message1.Use the or buttons to select the Fault message menu.2. If the fa
Bul. 937C HART Loop Converter Installation InstructionsService In the Service menu, you have the option of specifying basic device parameters.Select l
Bul. 937C HART Loop Converter Installation InstructionsTo protect parameterization from unauthorized changes, you can enable password protection. Info
Bul. 937C HART Loop Converter Installation InstructionsEditing device data: Default settingsIndicators during OperationThe isolated barrier displays t
Bul. 937C HART Loop Converter Installation InstructionsIn normal operation, the display shows:the current values of the HART variables PV, SV, TV, QV
Display Options for Current Output Values and HART VariablesTo select the displayed measured values or current output values, use the and buttons.
Technical SpecificationsDefault SettingsThe following table provides an overview of the default settings. Information about resetting the device to th
Menu Parameters Default setting Custom valueOutput --- Iout3Assignment disabledCharacteristic 4 - 20 NE43Start value 0.000End value 100.0Fault current
Reference to further documentationLaws, standards, or directives applicable to the intended use must be observed. In relation to hazardous areas, Dire
Publication 937-IN003A-EN-P - April 2014 (DIR 10001099005) 814570Copyright © 2014 Rockwell Automation, Inc. All r
Protection of the operating personnel and the overall system is not ensured if the product is not being used according to its intended purpose.The equ
The respective peak values of the field device and the associated apparatus with regard to explosion protection should be considered when conne
The device supplies field devices and can be connected in parallel to existing HART circuits.The device analyzes up to four HART variables (PV, SV, TV
Operating and indicating elementsProduct Specifications AssemblyBul. 937C HART Loop Converter Installation Instructions711 234 5629ERR PWR1 2OUT3 48ES