AC Line Filters
In addition to EMI/RFI safeguards inherent in the DC3RD
design, external filtering is required. Reliance Electric
requires the Corcom® AC line filters listed in Table 3. Use
model 5VR1 with drives rated for 3 ADC or below, and
model 20VV1 with drives rated for 10 ADC or below.
Table 3. AC Line Filters
Corcom
®
Model Number 5VR1 20VV1
Rated Current 5 A 20 A
Inductance 1.032 mH 0.88 mH
Capacitance
Line to Line 0.303 µF 0.303 µF
Line to Ground 0.011 µF 0.011 µF
Discharge Resistor 680 K 680 K
Wire the AC line filter within 0.25 meters of the drive. The
ground connection from the filter must be wired to solid
earth ground (resistance less than 500 ohms); not machine
ground. This is very important!
If the end-user is using a CE-approved motor, the correct
filter from Table 3 is all that is necessary to meet the
EMC directives listed herein.
54 CE Compliance
250-0285-rev1.qxd 4/26/00 9:36 AM Page 54