Configuring FactoryTalk Historian Live Data Interface Chapter 3
Rockwell Automation Publication HSELD-UM024A-EN-E–September 2013 17
To configure an FTLD Interface with the ICU:
1. Go to Start > All Programs > Rockwell Software > FactoryTalk
Historian SE > Interface Configuration Utility. The Interface
Configuration Utility dialog box appears.
2. On the Interface menu, click New Windows Interface
Instance from BAT File. The Open Interface
Configuration File dialog box appears.
3. Navigate to C:\Program Files\Rockwell Software\FactoryTalk
Historian\Server\PIPC\Interfaces\LDInterface.
4. Select the FTLDInt_FTLD.bat.bak file and click Open.
5. Click OK in the Interface Configuration Utility message
box to acknowledge the information on duplicated point
sources and ID combinations.
The FTLD Interface configuration is displayed on the
General page of the ICU.
6. From the Type list, select FTLDInt, if it has not been chosen
automatically.
Vista de pagina 16