18 Rockwell Automation Publication IASIMP-QS031A-EN-P - February 2012
Chapter 1 Prepare the PowerFlex 70 Drive Hardware
Configure the EtherNet/IP Adapter
The PowerFlex 70 EtherNet/IP network adapter requires a network IP address to operate on an
EtherNet/IP network. You use the BOOTP/DHCP server to assign an IP address.
1. Retrieve the MAC ID you recorded in step 1 on page 17
.
2. Start the BOOTP/DHCP utility.
3. From the Tools menu, choose
Network Settings.
4. Type the Subnet Mask of
the network.
The Gateway address, Primary
and/or Secondary DNS address,
and Domain Name fields are
optional.
5. Click OK.
The Request History panel appears with the hardware addresses of all devices issuing
BOOTP requests.
6. Select the appropriate device, that
is, the device with the MAC ID
that matches your PowerFlex 70
drive.