32 Rockwell Automation Publication IASIMP-QS031A-EN-P - February 2012
Chapter 2 Add a PowerFlex 70 Drive to an RSLogix 5000 Project
Test the PowerFlex 70 Drive Tags
1. Move the controller mode switch
to RUN.
2. Double-click Controller Tags.
3. On the Monitor Tags tab, expand
the PowerFlex 70 output tag and
change the ClearFault tag to 1 to
clear any initial faults.
4. Change the ClearFault tag
back to 0.
5. Expand the PowerFlex 70 input
tag and Verify that the
I.DriveStatus_Ready tag value is 1.
This tag indicates that the drive is
ready to start.