Chapter 5
Access status information
The controller supports status keywords you can use in your logic to monitor
specific events.
The status keywords are not case sensitive.
Because the status flags can change quickly, the Logix Designer application
does not display the status of the flags. For example, even when a status flag
is set, an instruction that references that flag is not highlighted.
You cannot define a tag alias to a keyword.
The following table lists the available key words.
To determine if Use
The value you are storing cannot fit into the destination because it is either:
Greater than the maximum value for the destination.
Less than the minimum value for the destination.
Important: Each time S:V goes from cleared to set, it generates a minor fault (type 4, code 4).
S:V
The instruction’s destination value is 0. S:Z
The instruction’s destination value is negative. S:N
An arithmetic operation causes a carry or borrow that tries to use bits that are outside the data type.
For example:
Adding 3 + 9 causes a carry of 1.
Subtracting 25 - 18 causes a borrow of 10.
S:C
This is the first, normal scan of the routines in the current program. S:FS
At least one minor fault has been generated.
The controller sets this bit when a minor fault occurs due to program execution.
The controller does not set this bit for minor faults that are not related to program execution, such as
battery low.
S:MINOR
Introduction
Rockwell Automation Publication 1756-PM015F-EN-P October 2014 53