Chapter 1 Major faults
To simplify access to the MajorFaultRecord attribute, complete these steps to
create a user-defined data type.
1. In the Controller Organizer, right-click User-Defined and choose New
Data Type.
2. On the New Data Type window, enter the data type information as shown
in the following table.
Data Type: FAULTRECORD
Name
FAULTRECORD
Description
Stores the MajorFaultRecord attribute or MinorFaultRecord attribute of the
PROGRAM object.
Members
Name Data Type Style Description
Time_Low DINT Decimal Lower 32 bits of the fault timestamp value
Time_High DINT Decimal Upper 32 bits of the fault timestamp value
Type INT Decimal Fault type (program, I/O, and so forth)
Code INT Decimal Unique code for the fault
Info DINT[8] Hex Fault specific information
3. Click OK.
22 Rockwell Automation Publication 1756-PM014G-EN-P October 2014