MAI32*A
D
October
200
5
13
Triguard
SC300E
MAI32*AD
32
-
Channel A/I Module Differential Input
SERVICING
SCOPE
System
repair
is
by
module
replacement.
Faulty
modules
are
not
repairable
in
the
fi
eld,
they
should
be
replaced
by
new
modules
and
returned
for
repair.
CAUTION
1
Before
fitting
a new
module
ensure
that
the
321/320
link
setting
is
the
same
as
that
on
the
old
module.
CAUTION
2
The
module
contains
components
that
may
be
electrostatically
sensitive,
it
should
be
transported
and
stored
in
its
original
packaging
material.
DIAGNOSIS
The
TriBuild
workstation
is
used
for
fault
diagnosis.
In
the
case
of
an
Input/Output
fault
the
Health
LED
on
the
faulty
module
will
be
extinguished.
CAUTI
ON
3
Do
not
use
a mains
-
powered
multimeter
on
the
front
panel
test
points.
CONFIGURATION
The
only
configuration
necessary
is
the
correct
location
of
the
321/320
Link
as
shown
in
Figure
1
-
1 Ensure
that
the
link
configuration
on
the
new
module
is
identical
to
that
on
the
old
module.
REMOVAL AND REPLACEMENT
Preparation
Before
removal
/replacement
ascertain
if
the
module
under
consideration
is
used
in
the
single
or
dual
hot
repair
configuration.
CAUTION
4
Failure
to
take
the
faulty
module
off
-
line
before
removing
it
from
the
chassis
could
trigger
a fault
alarm
or
cause
plant
shutdown.