SERVICING
SCOPE
Repair
is
by
module
replacement.
Faulty
modules
are
not
repairable
in
the
field.
They
should be
replaced
by
new
modules
and
returned
for
repair.
CAUTION
1
Before
fitting
a new
module
ensure
that
the
setting
of
the
configuration
lin
ks
are
the
same
as
that
on
the
old
module.
CAUTION
2
This
module
contains
components
that
may
be
electrostatically
sensitive.
It
should
be
transported
and
stored
in
its
original
packaging
material.
DIAGNOSIS
The
TriBuild
workstation
is
used
for
fault
diagnosis.
In
the
case
of
an
Input/Output
fault
the
Health
LED
on
the
faulty
module
will
be
extinguished.
PREPARATION
To
ascertain
whether
the
chassis
I/O
slot
containing
the
faulty
module
has
been
allocated
a
hot
repair
partner,
use
one
of
the
following
methods:
Check
the
system
drawings
Check
the
chassis
wiring
configuration
Use
the
I/O
chassis
Configuration
Report
on
the
TriBuild
workstation.
Where
there
is
a hot
repair
partner
allocation,
use
the
‘D
ual
-
slot
hot
repair’
procedure,
otherwise
use
the
‘Single
-
slot
hot
repair’
procedure.
CONFIGURATION
Before
fitting
a new
module
ensure
that
321/320
link
setting
is
the
same
as
that
on
the
old
module.
REMOVAL AND REPLACEMENT
CAUTION
3
Failure
to
take
the
faulty
module
off
-
line
before
removing
it
from
the
chassis
could
trigger
a fault
alarm.
CAUTION
4