Vista de pagina 0
ICS Regent+Plus
®
PD
-
7015
Industrial Control Services
1
DC Digital Output Module
24 VDC
(T7441A)
Issue 1,
March, 06
The DC digital output module provides control of 16 user
output loads. One type of module is available to interface to
outputs powered from a nominal 24 VDC field power su
pply.
Each module's triplicated I/O Safetybus interface ensures that
no Regent system failure can incorrectly apply power to an
output, and that no failure in the module can affect the
operation of the Regent system or other I/O modules in the
system.
Features
·
Sixteen output circuits, configured as two isolated groups of
eight circuits each.
·
Hot
-
replaceable.
·
Automatic self
-
testing of triplicated I/O Safetybus circuits and
many simplex logic circuits.
·
2 amp output circuits.
·
Individual front panel indicators on each module show
active/fault, shutdown, blown fuse, and output on/off status
(field side).
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
TÜV certified, Risk Class 5, non
-
interfering.
Vista de pagina 0
1 2 3 4 5 6 ... 12 13

Indice de contenidos

Pagina 1 - ICS Regent+Plus

ICS Regent+Plus® PD-7015 Industrial Control Services 1 DC Digital Output Module 24 VDC (T7441A) Issue 1, March, 06 The DC digital output module pro

Pagina 2 - Module Operation

DC Digital Output Module (T7441A) 10 Industrial Control Services Name Also called the tag name, this is the name used in the application program t

Pagina 3 - Front Panel Indicators

(T7441A) DC Digital Output Module PD-7015 Mar-06 11 control logic by using a contact element (or similar element) with the output point name. Mai

Pagina 4

DC Digital Output Module (T7441A) 12 Industrial Control Services Minimum Load 0 mA On State Drop 0.5 volts maximum @ 2 amps Surge Current 15 amps,

Pagina 5

(T7441A) DC Digital Output Module PD-7015 Mar-06 13 Safety Certified to DIN V VDE 0801 (non-interfering) and designed to meet UL 508 and CSA 22.2

Pagina 6 - Application

DC Digital Output Module (T7441A) 2 Industrial Control Services Module Operation A block diagram of a typical 24 VDC digital output module is sho

Pagina 7 - Fault Mode Jumper

(T7441A) DC Digital Output Module PD-7015 Mar-06 3 When the output is logically turned on, the field device is energized, and when the output is

Pagina 8 - Configuration

DC Digital Output Module (T7441A) 4 Industrial Control Services Active and Fault Status Indicators These green and red LEDs indicate the overall

Pagina 9

(T7441A) DC Digital Output Module PD-7015 Mar-06 5 Figure 2. 24 VDC Digital Output Module.

Pagina 10 - Programming

DC Digital Output Module (T7441A) 6 Industrial Control Services Application Simplex Configuration Digital output modules provide a suitable inter

Pagina 11

(T7441A) DC Digital Output Module PD-7015 Mar-06 7 Fault Mode Jumper The fault mode jumper is located behind the ID switch cover in the lower le

Pagina 12 - Industrial Control Services

DC Digital Output Module (T7441A) 8 Industrial Control Services Figure 4. Installing Slot Keys. Configuration Each output module is configure

Pagina 13

(T7441A) DC Digital Output Module PD-7015 Mar-06 9 1) Set the Module Type: Position the cursor on the module slot you wish to define. Choose S

Comentarios a estos manuales