(T7441A)
DC Digital Output Module
PD
-
7015
Mar
-
06
11
control logic by using a contact element (or similar element)
with the output point nam
e.
Maintenance
No periodic maintenance or calibration is required for this
module.
Fuses for each output are located within the module. To
replace a blown fuse the output module must be removed from
the I/O chassis and opened. To open the output module,
remove four screws from the side of the module’s clamshell.
Remove the blown fuse from its retaining clips (on the circuit
board) and replace it.
To prevent damage to the module, replacement fuses must be
of the same rating and type (see Specifications, b
elow).
To prevent electrostatic damage to sensitive module circuits,
maintenance personnel should always use the proper anti
-
static work areas and grounding straps when handling or
working with circuit boards.
Safety Considerations
The DC digital output module is TÜV certified as non
-
interfering, and can be used in a safety system for simplex
non
-
safety critical outputs. For safety critical outputs,
guarded output modules should be used (model T3461A,
T3481 or T3485 are recomm
ended).
Specifications
16 circuits divided into two
groups of 8 circuits each
2 amps maximum per output
0°
to 60
°
C