Triguard
SC300E
BATTERY
REPLACEMENT
Fresh
batteries
will
sustain
SRAM
for
a total
of
about
six
months
(either
in
one
long
stretch,
or
in
several
shorter
stretches).
The
backup
batteries
should
be
replaced
where
it
is
known
that
the
total
battery
drain
period
is
approaching
six
months
or
once
every
five
years
(whichever
occurs
first).
If
the
SC300E
System
is
Operating
1.
Remove
one
of
the
three
MPPs.
2.
Remove
and
safely
dispose
of
both
batteries.
3.
Wait
about
5 minutes
for
any
capacitance
in
the
system
to
discharge.
4.
Ensuring
the
correct
polarity
Figure
1
-
1
,
fit
the
new
batteries.
5.
Replace
the
MPP
and
perform
a war
m start.
6.
Repeat
the
above
procedure
for
each
of
the
remaining
MPPs
in
turn.
If
the
SC300E
System
is
Not
Operating
If
the
system
is
not
powered
up,
the
data
in
SRAM
is
being
supported
by
the
backup
batteries.
To
preserve
this
data
it
is
important
not
to
remove
both
batteries
at
once.
If
only
one
battery
is
fitted,
install
a new
battery
in
the
vacant
slot
before
removing
the
old
battery.
Comentarios a estos manuales