(T3454)
AC Isolated Digital Output Module
PD
-
6018
Mar
-
06
13
Specifications
Safetybus Power
0.75 load units
Number of Outputs
8 circuits, individually
isolated
Voltage Range
90 to 130 VAC
Frequency Range
47 to 63 Hz
Load Current
2 amps maximum per output
0°
to 60
°
C
16 amps maximum per
module 0
°
to 40
°
C, derated
linearly to 12 amps at 60
°
C
Minimum Load
50 mA
On S
tate Drop
2.0 volts maximum
Surge Current
15 amps, 20 msec
Output Leakage
2.5 mA maximum
Fusing
One 3 A, 250 V, fast
-
acting
(3AG) per output, located
inside module
Turn
-
On Delay
½ AC cycle, maximum
Turn
-
Off Delay
½ AC cycle, maximum
Heat Dissipation
32 Watts, 107 BTUs/hour
Over Voltage Protection
275 VAC, continuous
Isolation
2500 volts minimum (field
wiring to control logic)
2500 volts minimum
(channel to channel)
Operating Temperature
0°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-
40
°
to 85
°
C
(-
40
°
to 185
°
F)