AC Isolated Digital Output Module
(T3454)
2
Industrial Control Services
The processor modules send triplicated write data commands
to the output module over the I/O Safetybus. The processors’
addressing data and data write commands are voted by the
module (preventing I/O Safetybus failures upstream from the
mo
dule from affecting module operation). The voted result is
then passed to the I/O bus interface logic.
Figure
1
. Block Diagram of 110 VAC Isolated Digital Output Module.
The voted output data from the I/O bus interface logic is then
used to drive the output circuits. Zero crossing turn
-
on
TRIAC drivers are used to convert the logic level output drive
signals to switch 110 VAC power to load devices.
When the output is logically turned on, the field d
evice is
energized, and when the output is logically turned off, the
field device is de
-
energized.
Optical isolation between the module’s logic and field circuits
provides logic
-
to
-
field isolation
protecting the output
module from field signal over voltages, transients, and other
electrical disturbances. It also provides a safety barrier
between the primary field voltages and user accessible
circuits. Additionally each output is isolated from the other