ICS Regent® PD-6021 Industrial Control Services 1 AC Guarded Digital Output Module 110 VAC (T3464) Issue 1, March, 06 AC Guarded digital output mod
AC Guarded Digital Output Module (T3464) 10 Industrial Control Services Fault Tolerant Configuration For fault tolerant operation, two Guarded mod
(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 11 Figure 5. Fault Tolerant Configuration with Redundant Actuators. Field Wiring Fiel
AC Guarded Digital Output Module (T3464) 12 Industrial Control Services Figure 6. Fail-Safe Field Wiring.
(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 13 Figure 7. Fault Tolerant Field Wiring.
AC Guarded Digital Output Module (T3464) 14 Industrial Control Services Fault Mode Jumper The fault mode jumper is located behind the ID switch co
(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 15 Figure 8. Installing Slot Keys. Configuration Each output module is configured usi
AC Guarded Digital Output Module (T3464) 16 Industrial Control Services 1) Set the Module Type: Position the cursor on the module slot you wish t
(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 17 Name Also called the tag name, this is the name used in the application program to ref
AC Guarded Digital Output Module (T3464) 18 Industrial Control Services To program fault tolerant outputs two output coils driven by the same cont
(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 19 Table 3. Initialization Sequence. Step Display Description 1 8.8.8.8. Display test.
AC Guarded Digital Output Module (T3464) 2 Industrial Control Services replaced while the other Guarded module continues to control the loads wit
AC Guarded Digital Output Module (T3464) 20 Industrial Control Services Table 4. Operating Diagnostic Messages. Display Description AC AC quality
(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 21 Load Current (maximum) 1 amp maximum per output 0° to 40° C, derated linearly to 0.5 a
AC Guarded Digital Output Module (T3464) 22 Industrial Control Services Isolation 2500 volts minimum (field wiring to control logic) 2500 volts mi
(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 3 the TRIAC will be de-energized. If the TRIAC itself fails shorted when commanded off,
AC Guarded Digital Output Module (T3464) 4 Industrial Control Services Table 1. Output States After Switch Failure. Case Commanded Output Sta
(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 5 module error indication at the processor modules and a module fault indication at the
AC Guarded Digital Output Module (T3464) 6 Industrial Control Services the output switch's ability to conduct current (through an internal d
(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 7 Figure 2. AC Guarded Output Module.
AC Guarded Digital Output Module (T3464) 8 Industrial Control Services Diagnostic Message Display This four-digit display provides additional fau
(T3464) AC Guarded Digital Output Module PD-6021 Mar-06 9 current flows through the neutral wire, so it is important to size both the line and n