AC Guarded Digital Output Module
(T3464)
20
Industrial Control Services
Ta
ble
4
. Operating Diagnostic Messages.
AC quality problem (i.e. frequency is out of tolerance, frequency
is unstable, or phase difference between output groups 1
-
8 and
9
-
16).
AC power failure at field terminals A/B (output group 1
-
8).
AC power failure at field terminals C/D (output group 9
-
16).
Outputs are shut down (off). Caused by the loss of controller
communications or the module is not configured in the system.
Outputs are held at last stat
e. Caused by the loss of controller
communications.
Open load on output
nn
. Displayed only when output is on.
Open circuit on output
nn
. Switch is not able to close.
Short circuit on output
nn
. Switch is not able to open. The
crowbar switch was activated to blow the fuse. Blown fuse
message is suppressed.
Safety Considerations
Although the AC Guarded output modules provide extensive
diagnostics and testing features, they have only been TÜV
certified to Risk Class 5 as non
-
interfering. For safety
systems that require TÜV approved equipment, the T3484
Monitored Guarded output module is recommended.
Specifications
16 circuits divided into two
groups of eight
1º maximum between group
1
-
8 and group 9
-
16