ICS Regent+Plus
®
PD
-
7018
Industrial Control Services
1
AC Isolated Digital Output Module
110 VAC
(T7454)
Issue 1,
March, 06
The AC isolated digital output module provides control of
eight isolated user output loads. One type of module is
available to interface to outputs powered from is
olated 110
VAC field power supplies. Each module's triplicated I/O
Safetybus interface ensures that no Regent system failure can
incorrectly apply power to an output, and that no failure in
the module can affect the operation of the Regent system or
other I/O modules in the system.
Features
·
Eight isolated 110 VAC output circuits.
·
Hot
-
replaceable.
·
Automatic self
-
testing of triplicated I/O Safetybus circuits
and
many simplex logic circuits.
·
2 amp output circuits.
·
Zero
-
cross load switching.
·
Individual front panel indicators on each module show active
and fault, shutdown, blown fuse, and output on/off status (logic
side).
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
TÜV certified, Risk Class 5, non
-
interfering.
Module
Operation
A block diagram of a typical 110 VAC isolated digital output
module is shown in Figure
1
.
Vista de pagina 0
1 2 3 4 5 6 ... 12 13

Indice de contenidos

Pagina 1 - ICS Regent+Plus

ICS Regent+Plus® PD-7018 Industrial Control Services 1 AC Isolated Digital Output Module 110 VAC (T7454) Issue 1, March, 06 The AC isolated digital

Pagina 2 - Industrial Control Services

AC Isolated Digital Output Module (T7454) 10 Industrial Control Services Name Also called the tag name, this is the name used in the application p

Pagina 3

(T7454) AC Isolated Digital Output Module PD-7018 Mar-06 11 control logic by using a contact element (or similar element) with the output point n

Pagina 4

AC Isolated Digital Output Module (T7454) 12 Industrial Control Services Specifications Safetybus Power 0.75 load units Number of Outputs 8 circu

Pagina 5

(T7454) AC Isolated Digital Output Module PD-7018 Mar-06 13 Operating Humidity 0 to 95% relative humidity, non-condensing Vibration 10 to 55 Hz:

Pagina 6 - Application

AC Isolated Digital Output Module (T7454) 2 Industrial Control Services The processor modules send triplicated write data commands to the output

Pagina 7 - Fault Mode

(T7454) AC Isolated Digital Output Module PD-7018 Mar-06 3 outputs, to operate load devices powered from isolated field power supplies. Each out

Pagina 8 - Configuration

AC Isolated Digital Output Module (T7454) 4 Industrial Control Services Shutdown Indicator Upon loss of communications with the controller, outpu

Pagina 9

(T7454) AC Isolated Digital Output Module PD-7018 Mar-06 5 Figure 2. 110 VAC Isolated Digital Output Module.

Pagina 10 - Programming

AC Isolated Digital Output Module (T7454) 6 Industrial Control Services Application Simplex Configuration Isolated digital output modules provide

Pagina 11 - Safety Considerations

(T7454) AC Isolated Digital Output Module PD-7018 Mar-06 7 Fault Mode Jumper The fault mode jumper is located behind the ID switch cover in the

Pagina 12 - Specifications

AC Isolated Digital Output Module (T7454) 8 Industrial Control Services Figure 4. Installing Slot Keys. Configuration Each output module is c

Pagina 13

(T7454) AC Isolated Digital Output Module PD-7018 Mar-06 9 1) Set the Module Type: Position the cursor on the module slot you wish to define.

Comentarios a estos manuales

Sin comentarios