Rockwell-automation T8160 Trusted TMR Interface Manual de usuario Pagina 1

Busca en linea o descarga Manual de usuario para Equipo Rockwell-automation T8160 Trusted TMR Interface. Rockwell Automation T8160 Trusted TMR Interface User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 2
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
SDS-8160
Trusted
TM
Industrial Control System
Trusted
TM
TMR Interface-T8160
Issue 5 Jan 2006
FRONT PANEL
DESCRIPTION
The Trusted
TM
TMR Interface
provides an interface between a
Trusted
TM
Controller and Regent,
Regent+Plus I/O systems. The
module supports the existing Regent
I/O Safetybus, and the use of all
Regent and Regent+Plus I/O
modules as part of an I/O sub-
system.
The module consists of three identical
processor sub-systems containing a
Bus Interface, an I/O processor with
its associated memory, and a power
supply.
Each processor sub-system has an
interface to the triplicated Inter-
Module Bus (IMB) and I/O Safetybus.
The I/O Processors interface with the
Safetybus, linking the field I/O
modules to the Trusted
TM
TMR
Processor.
The three processor sub-systems
operate in lock-step synchronization,
providing 2-oo-3 hardware voting on
every data exchange between the
Trusted
T
M
TMR Processor and the
I/O sub-system. This ensures
uncompromised fault detection and
error-free operation.
The triplicated Power Supply Unit
receives dual redundant +24v dc
supplies from the Trusted
TM
Controller backplane, and converts
the supply to the logic levels required
by the module circuits. The module is
capable of operating with a failure of
either of the redundant power feeds.
The module scans the I/O sub-system
and exchanges data with the
Trusted
TM
TMR Processor. Data
from inputs are read from the I/O
modules in the I/O sub-system.
Outputs are driven by transmitting
data through the I.O Processor to the
I/O module. Output Data from the
Trusted
TM
TMR Processor to the I/O
module is in the required format for
Regent+Plus.
Communications between the
Trusted
TM
TMR Processor and the
I/O Processor are maintained through
shared RAM used as amail box for
data transfers between the two.
FEATURES
Supports the use of all Regent
and Regent+Plus I/O modules
Triplicated interfaces to
Trusted
T
M
TMR Processors and
Regent+Plus I/O sub-systems
Hot replaceable
Module fault and status
indicators
IEC 61508, SIL 3 safety
applications
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - FEATURES

SDS-8160 TrustedTM Industrial Control System TrustedTM TMR Interface-T8160 Issue 5 Jan 2006 FRONT PANEL DESCRIPTION The TrustedTM TMR Interface pro

Pagina 2

SDS-8160 TrustedTM Industrial Control System TrustedTM TMR Interface-T8160 ICS Triplex Technical data sheets are intended for information and guidan

Comentarios a estos manuales

Sin comentarios