Rockwell-automation T8432 Trusted Dual Vdc Analogue Input Module - 60 Manual de usuario Pagina 21

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 33
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 20
Trusted
TM
Module T8432
Issue 16 Apr 10 PD-T8432 21
3.2.5. Rack 5: LINE_FLT
Channel Description
1 Field input channel 1 line fault
2
Field input channel 2 line fault
60 Field input channel 60 line fault
Table 11 Rack 5: LINE_FLT
The line fault input state is reported as true (logic1) for a line fault condition (under-range, or
overrange condition). The logic state is the majority voted value.
3.2.6. Rack 6: DISCREP
Channel Description
1 Discrepancy status inputs 1 to 16
2 Discrepancy status inputs 17 to 32
3 Discrepancy status inputs 33 to 48
4 Discrepancy status inputs 49 to 60
Table 12 Rack 6: DISCREP bit descriptions
Each of the words reports the discrepancy status of several input channels. The corresponding bit
within the word is set to ‘1 when a discrepancy condition is detected on that input channels input state
(rack 2).
Vista de pagina 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 32 33

Comentarios a estos manuales

Sin comentarios