Rockwell-automation T8472 Trusted TMR 120V ac Isolated Output Module Manual de usuario Pagina 18

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 28
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 17
Trusted
TM
Module T8472
Issue 13 Sep 11 PD-T8472 18
3.2.7. Rack 7: Housekeeping
Channel
Description
FCR Units (Full Scale Range)
1
A
24V2 Output Voltage -32768 32767 mV
2
B
3
C
4
A
Internal supply voltage (post regulator) -32768 32767 mV
5
B
6
C
7
A
Internal supply current (post regulator) -32768 32767 mA
8
B
9
C
10
A
Output voltage (post isolation) -32768 32767 mV
11
B
12
C
13
A
24V1 Output Voltage -32768 32767 mV
14
B
15
C
16
A
HIU Board Temperature -32768 32767 -
17
B
18
C
19
A
Front Panel Load Current -32768 32767 mA
20
B
21
C
22
A
SmartSlot Link Voltage -32768 32767 mV
23
B
24
C
25
A
FIU Output Group 1 Field Supply Voltage -32768 32767
26
B
/125
27
C
V AC
28
A
FIU Output Group 2 Field Supply Voltage -32768 32767
29
B
/125
30
C
V AC
31
A
Field Supply Frequency -32768 32767 Hz
32
B
33
C
34
A
FIU Board Temperature, Output Group 1 Average -32768 32767 -
35
B
36
C
37
A
FIU Board Temperature, Output Group 1 Peak -32768 32767 -
38
B
39
C
40
A
FIU Board Temperature, Output Group 1Peak Channel # -32768 32767
41
B
42
C
43
A
FIU Board Temperature, Output Group 2 Average -32768 32767 -
44
B
45
C
46
A
FIU Board Temperature, Output Group 2 Peak -32768 32767 -
47
B
48
C
49
A
FIU Board Temperature, Output Group 2Peak Channel -32768 32767
50
B
51
C
52
A
Update Count (Diagnostic only) -32768 32767
53
B
54
C
55
A
Diagnostic error code
56
B
57
C
Table 12 Rack 7: Housekeeping descriptions
Note: Slice A, B and C not applicable for all channels
Vista de pagina 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 27 28

Comentarios a estos manuales

Sin comentarios