6. 120VAC Digital Output Module Specification
System Supply Voltage Range 20 to 32Vdc
C
ircuit Type Fault tolerant, fully triplicated with quad output
switch circuits.
Number of Outputs 16 Channels
Independent Power Groups 2 each of 8 outputs
Operational Output/Field Voltage Range 90 to 150VAC, 47Hz < freq < 63Hz
Output Voltage
Measurement Range 150VAC(RMS)
Maximum Withstanding 175VAC(RMS)
Output Current Rating
Continuous ( Imax per channel )
Continuous ( Imax per power group )
Channel surge
0.5A
4A
8A peak (1 AC cycle)
Minimum On State Load Current 10mA
Power Consumption
System Supply (24V)
17W
Field Common Isolation
Sustained Working
Maximum Withstanding
±250Vdc
±2.5kVdc
Output Off State Leakage 2mA max at 150VAC
Output On State Switch Voltage Drop 1VAC (RMS) max at 0.5A loading
Output Short Circuit Protection Electronic
Output Turn-on/off Delay 1.5 AC cycle max. (zero crossing)
Channel Monitor Update Every 16 AC cycles
Sequence of Events
Event Resolution
1ms
Channel Test Interval 1 minute
Intrinsic Safety External barrier
Operating Temperature
-5°C to 60°C (23°F to 140°F)
Non-operating Temperature
-25°C to 70°C (-13°F to 158°F)
Temperature change 0.5ºC/min
Operating Humidity 5 – 95% RH non-condensing
Environmental Specifications Refer to document 552517
Dimensions
Height
Width
Depth
266mm (10.5ins)
31mm (1.2ins)
303mm (12ins)
Weight 1.342Kg (3lb)