Rockwell-automation 1203 Serial Communications Module Series A Manual de usuario Pagina 40

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 68
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 39
Chapter 5
Configuration and Interfacing
5-4
Table 5.C
Data Table Structure for PLC-2 Style Addressing
Parameter
Number
PLC-2 Style Address
Decimal (Octal)
Description of
Location’s Purpose
1 – 7039
512 + Parm #
(1001 to 16577)
Parameter Value Read
(16600 to 16777) Status of Last Parameter Write
1 – 7039
7680 + Parm #
(17001 to 34577)
Parameter Read Full
(34600 to 34677) Block Transfer Emulation Area
(34700) Logic Command/Status
(34701) Reference/Feedback
(34702) Datalink A1
(34703) Datalink A2
(34704) Datalink B1
(34705) Datalink B2
(34706) Datalink C1
(34707) Datalink C2
(34710) Datalink D1
(34711) Datalink D2
(34712) #ENQs
(34713) #NAKs
(34714) Message TIMEOUT (mS)
(34715) Application TIMEOUT (Seconds)
(34716 to 37677)
Reserved Area for Future
Expansion
(37700 to 37777) System Area
NOTE: The address locations shown in this table are not limited to PLC-2
commands and may be used by any device capable of generating them.
Vista de pagina 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 67 68

Comentarios a estos manuales