Rockwell-automation 1336T Function Block Prog. Manual, Series A/B Manual de usuario Pagina 102

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 180
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 101
Function Block Library 4–40
1336 FORCE — 5.9 August 1995
Example 1 — KI & KP = 1 — Horizontal Scale = 100mS/Division
In Example 1, all gains are at unity — KI and KP are set to 4096, Gain is set to 2048. Preset
is set to –32767.
A PI CTRL Output
+32767 "
32767 "
PI CTRL Input (+)
B
0 "
A–––––––––––––––––––––––––––––––––––– 1 Second –––––––––––––––––––––––––––––––––––"
When the input difference steps from 0 to +32767, the proportional term responds by going
from –32767 to zero within one task interval. The Output then takes approximately one se-
cond to integrate up to the Max setting of +32767.
Example 2 — KI & KP = 1/4 — Horizontal Scale = 1S/Division
In Example 2, the KI and KP gains are at 1/4 (1024), while Gain is set to unity (2048). Preset
has been set to –32767.
+32767 "
32767 "
24576 "
A––––––– 3 Seconds ––––"
0 "
A PI CTRL Output
Y
PI CTRL Input (–)
Y
PI CTRL Output
+32767 "
When the input difference steps from 0 to –32767, the proportional term responds by
immediately going to a value of –24576. After 3 seconds, the Output integrates to zero. With
KI at 1/4 gain, it will accumulate at a rate of approximately 8191 units-per-second with an
input difference of +32767. Note that it takes (4) seconds to integrate from 0 to +32767.
PI CTRL
(continued)
Vista de pagina 101
1 2 ... 97 98 99 100 101 102 103 104 105 106 107 ... 179 180

Comentarios a estos manuales

Sin comentarios