6 XM-947 Dynamic Vibration Terminal Base
Publication GMSI10-IN027A-EN-P - May 2010
Power Requirements
Power Supply
Requires a 24Vdc (±10%) power source per the following table.
European Zone 2 Certification
If appropriately marked, this equipment is intended for use in potentially explosive
atmospheres as defined by European Union Directive 94/9/CE.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 50021 (1999).
Observe the following additional Zone 2 certification requirements:
This equipment is not resistant to sunlight or other sources of UV
radiation.
The secondary of a current transformer shall not be open–circuited.
The marking “ALCR” is to be considered “as applicable” to individual
products.
Equipment of lesser Enclosure Type Rating must be installed in an
enclosure providing at least IP54 protection when applied in Class I,
Zone 2 environments.
This equipment must be powered by energy limited associated
equipment as defined in EN 50021 when applied in Class I, Zone 2
environments.
Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in
Class I, Zone 2 environments.
XM Power Supply Requirements
Protection
Listed Class 2 rated supply, or
Fused* ITE Listed SELV supply, or
Fused* ITE Listed PELV supply
Output Voltage 24Vdc ± 10%