Auxiliary Contact Assembly Set-Up
1. Clamp the contactor closed from the back of the unit, using a
C-Clamp (or clamping fixture, part no. 80154-149-51).
2. Insert a 0.030” (0.76 mm) feeler gauge between the plastic
auxiliary contact actuator and the steel actuator plate.
(See Figure 8)
Figure 8 – Set-up of the Auxiliary Contact Assembly
3. Slide the assembly fully forward, until the contacts have fully
engaged.
4. Secure the assembly in place by tightening the auxiliary assembly-
retaining bolt.