8 Electrically Held to Mechanical Latch Contactor • Retrofit Instructions
1502-IN001%-EN-P – -XQH
Figure 10 – Contactor (rear view) showing wires to be wire-tied
Electrical Test
1. Connect the contactor to the control using the supplied umbilical
cord.
2. Test the latch by electrically engaging the contactor using the
control circuit.
3. If the contactor fails to latch, re-calibrate the gaps between the
auxiliary contacts and contact actuator plate and the gap between
the latch roller and contactor armature plate.
Figure 11 – Complete Contactor after Conversion