Monitoring and Troubleshooti ng 5-3
1503-UM052D-EN-P – Ju n e 2013
Table 5.A – IntelliVAC Status Indication (Series C only)
Conditions
Description
Module Status
Contactor Status
LED Color Relay LED Color Relay
Normal Healthy Module and Contactor OPEN Green Closed Off Open
Normal Healthy Module and Contactor CLOSED Green Closed Yellow Closed
Warning Invalid Command Present Yellow Closed Off Open
Warning Mechanical Latch Fail to Trip Yellow Open Yellow Closed
Fault Power Up with Contactor CLOSED Red – Flash 2 Open Yellow Closed
Fault Contactor Fails to Pick Up Green Open Red – Flash 1 Open
Fault Contactor Drop Out During Hold Green Open Red – Flash 2 Open
Fault Long Contactor Drop Out Time Green Open Red – Flash 3 Open
Fault Microcontroller Malfunction Red Open Red Open
Fault Power Up with Invalid Dip Switch Configuration
Red – Flash 1 ⊂
Open Off Open
Fault Undervoltage with a CLOSE Command Present Red Open Off Open
Warning = Recoverable Condition – Remove and retry offending signal
Fault = Non-recoverable condition – Module power must be removed and re-applied.
Flash 1 = 1 Flash Red LED followed by a pause.
Flash 2 = 2 Consecutive Red LED flashes followed by a pause.
Flash 3 = 3 Consecutive Red LED flashes followed by a pause.
Only for Electrically Held Contactor
Invalid Command Types:
1. Close, Jog or Trip commands present during power up sequence.
2. Close or Jog command re-applied too quick ly (before contactor opening sequence is verified).
Allow at least 60 msec, plus drop out delay time, before re-applying these signals.
NOTE: Contactor will only respond to a close command re-applications after the re-start delay timer has expired.
3. Close and Trip commands present simultaneously (valid with Mechanical Latch contactors only).
Undervoltage conditions are defined on page 3-17.