Rockwell-automation 1503 IntelliVAC Contactor Control Module - Series Manual de usuario Pagina 50

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 53
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 49
Typical Contactor Drop-out Times A-3
1503-UM052D-EN-P June 2013
Table A.1 Typical Contactor Drop-out Time Settings (cont.)
Fuse Rating Contactor Drop-out Time Setting (msec)
Voltage Designation 400A 800A
7200
2R
50
50
3R
4R
6R
9R
12R
18R
75
24R
150
32R
240 *
38R
75
48X
150
57X
200
2 x 18R
50
2 x 24R
130
2 x 32R
240 *
2 x 38R
2 x 48X
2 x 57X
8250
10E
50 50
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
Fuse not suitable for use with contactor.
Note: The drop-out time is chosen to be equal to or greater than the
intersection of the rated contactor interrupting current and the
fuse melt time curve (except where noted *)
Vista de pagina 49
1 2 ... 45 46 47 48 49 50 51 52 53

Comentarios a estos manuales

Sin comentarios