5-6 Monitoring and Troubleshooting
1503-UM 052D-EN-P Ju ne 2013
Contactor Status (cont.)
Table 5.C Module Troubleshooting (cont.)
Problem or Trip Indicated Indication of the following conditions Possible Solutions
Contactor opens during operation
Motor Protection activated
Investigate and reset.
Stop command initiated
Verify circuit
Module Status LED ‘Red (Series C)
or ‘Yellow Flashing’ (Series D)
Undervoltage fault (no TDUV), control voltage dipped
below trip point. Verify voltage levels are 110 to 240
VAC, 110 to 250 VDC.
With external capacitor and TDUV feature activated,
undervoltage condition for longer than programmed
TDUV time. Undervoltage fault activated.
Module Status LED ‘Greenand Contactor Status LED
‘Red Flash 2(Series C)
or
Module Status LED ‘Yellow
R2’ and Contactor Status
LED ‘Off
Contactor Status feedback between Terminals 11 and
12 on the IntelliVAC has closed. The IntelliVAC will de-
energize the coil, thinking the contactor has opened
for other reasons.
Both status LEDs ‘Off
Check control voltage and internal control fuse. (Refer
to Figure 4.1 for location.)
Contactor does not open (mechanical latch)
Module Status LED ‘Yellow and Contactor Status LED
‘Yellow’
Trip mechanism is damaged. Inspect and replace if
needed.
Check for loose connections in the control circuit.
Contactor does not open
(electrically held)
Series C Module Status LED ‘Green’ and Contactor
Status Red Flash 3
Series D Module Status LED ‘Yellow R3 and
Contactor Status LED ‘Yellow
Contactor welded or mechanisms binding. Inspect and
repair if needed.
Refer to Table 5.A (Series C) or Table 5.B (Series D) for definition of Module
LED states.
Table 5.D Minimum IntelliVAC Operational Supply Voltages
Voltage Level
Contactor Rating
(Amps)
Minimum Voltage
(VAC, 47 to 63 Hz)
Pick-Up 400/800 95
Drop-Out 400/800 75
Trip (Mechanical Latch)
400 70
800 80