POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 111
1734-OE2V
2 Channel Analog Voltage Output
Configuration Data Data Type Default
Value
Valid Data Values
Fault Value Channel 0 INT 0 -32,768…32,767
Program Value Channel 0 INT 0 -32,768…32,767
Low Engineering Channel 0 INT 0 -32,768…32,767
High Engineering Channel 0 INT 10,000 -32,768…32,767
Low Limit Channel 0 INT -32,768 -32,768…32,767
High Limit Channel 0 INT 32,767 -32,768…32,767
Range Type Channel 0 SINT 1 1=0…10V
3=-10…+10V
Fault Mode Channel 0 SINT 1 0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Idle Mode Channel 0 SINT 1 0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Limit Alarm Latch Channel 0 SINT 0 0=No Latching
1=Alarms Latch
Alarm Disable Channel 0 SINT 0 0=Alarms Enabled
1=Alarms Disabled
Fault Value Channel 1 INT 0 -32,768…32,767
Program Value Channel 1 INT 0 -32,768…32,767
Low Engineering Channel 1 INT 0 -32,768…32,767
High Engineering Channel 1 INT 10,000 -32,768…32,767
Low Limit Channel 1 INT -32,768 -32,768…32,767
High Limit Channel 1 INT 32,767 -32,768…32,767
Range Type Channel 1 SINT 1 1=0…10V
3=-10…+10V
Fault Mode Channel 1 SINT 1 0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Idle Mode Channel 1 SINT 1 0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value