Rockwell-automation 1734-IV4/C Point I/O Source Input Module Installat Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 24
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
POINT I/O Source Input Module 17
Publication 1734-IN052D-EN-E - February 2005
Indication Probable Cause
Network Status
Off Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator
Flashing Green Device is on-line but has no connections in the established
state.
Green Device on-line and has connections in the established state.
Flashing Red One or more I/O connections in timed-out state
Red Critical link failure - failed communication device. Device
detected error that prevents it communicating on the network.
Flashing Red/
Green
Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identify Communication
Faulted Request - long protocol message.
Indication Probable Cause
I/O Status
Off Input is in the off-state.
Yellow Input is in the on-state.
Vista de pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 23 24

Comentarios a estos manuales

Sin comentarios