Variable Content
TTL:Chap
C–3
Publication
17466.8 - April 1997
For the 1746-NI4, input selection (voltage or current) is made via a
switch. For the 1746-NI8, input selection (voltage or current) is
made via a switch and a configuration word is used to define the
other operating parameters for the module. The 1746-NI4 does not
employ a configuration word.
To configure the 1746-NI8 for the same input type as the 1746-NI4,
use the following configuration word. For voltage input you must
select ±10V dc, and for current input you must select ±20 mA.
Define a configuration word for channels 0–7 on the 1746-NI8
module.
Input Type
Data Format
Open Circuit
Filter Frequency
Channel Enable
Not Used
Current Input
Voltage Input
1112131415
0000
910 8 67450123
0000
Bit Number
1100 01111000
1100 01100000
Bit Definitions for Converting from 1746NI4 to 1746NI8:
Bits 0-2
Input Type
000 = ±10V dc 110 = ±20 mA
Bits 3- 5 Data Format 011 = 1746NI4 data format
Bits 6 and 7 Open Circuit
00 = zero (the open circuit option is not available for the ±20 mA data type)
Bits 8-10 Filter Frequency 100 = 10 Hz
Bit 11 Channel Enable 0 = channel disabled 1 = channel enabled
Bits 12-15 Not Used 0000 = always make this setting
See chapter 5 for more detailed information on channel
configuration.
To convert your ladder program from the 1746-NI4s to a 1746-NI8,
you only need to change the module addressing. Change the
addresses in the program (slot and word sub element number) to
reflect the location of the new module.
See chapter 6 for more information on ladder programming.
Channel Configuration
Ladder Program