SLC 500 EtherNet/IP Adapter 15
Publication 1747-IN521B-EN-E - January 2013
Specifications
Ethernet Communication
Attribute Value
EtherNet communication rate 10/100 Mbits/s, half or full-duplex
Ethernet ports 2, configured as Embedded Switch
Ethernet network topologies supported Star, Tree, Daisy chain/Linear, and Ring
Ethernet connector RJ-45, Category 5
Ethernet cable Category 5: shielded or unshielded
General Specifications
Attribute Value
Module location Always at Slot 0 (leftmost slot) on chassis
Current consumption, backplane 470 mA @ 5V DC
Thermal dissipation 2.49 W = 8.4962 Btu (IT)/hour
Isolation voltage 50V (continuous), Basic Insulation Type
Dimensions (HxWxD), approx. 145.3 x 34.8 x 130.8 mm
(5.72 x 1.37 x 5.15 in.)
Enclosure type rating None (open-style)
Wiring category
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication 1770-4.1
.
1 – on communication ports
Weight, approx. 168 g (0.37 lbs.)
North American temp code T3C