INSTRUCTION ERRORS
Error
Code
Fault Description
02H
Target node is busy. The MSG instruction will automatically reload. If other
messages are waiting, the message is placed at the bottom of the stack.
03H Target node cannot respond because message is too large.
04H
Target node cannot respond because it does not understand the command
parameters OR the control block may have been inadvertently modified.
05H Local processor is offline (possible duplicate node situation).
06H Target node cannot respond because requested function is not available.
07H Target node does not respond.
08H Target node cannot respond.
09H Local modem connection has been lost.
10H
Target node cannot respond because of incorrect command parameters or
unsupported command.
11H Local file has constant file protection.
12H Local channel configuration protocol error exists.
13H Local MSG configuration error in the Remote MSG parameters.
14H Local communication driver is incompatible with the MSG instruction.
15H Local channel configuration parameter error exists.
16H Target or Local Bridge address is higher than the maximum node address.
17H Local service is not supported.
18H Broadcast (Node Address 155) is not supported.
19H
Improperly formatted Logical ASCII Address string. String not properly
terminated with a NULL character or the string length does not match the
value in the length parameter.
20H PCCC Description: Host has a problem and will not communicate.
30H
PCCC Description: Remote station host is not there, disconnected, or shut
down.
37H Message timed out in local processor.
38H Message disabled pending link response.
40H PCCC Description: Host could not complete function due to hardware fault.
50H Target node is out of memory.
60H Target node cannot respond because file is protected.
70H PCCC Description: Processor is in Program mode.
80H
PCCC Description: Compatibility mode file missing or communication zone
problem.
90H PCCC Description: Remote station cannot buffer command.
B0H PCCC Description: Remote station problem due to download.
C0H PCCC Description: Cannot execute command due to active IPBs.
D0H
No IP address configured for the network, -or-
Bad command – unsolicited message error, -or-
Bad address – unsolicited message error, -or-
No privilege – unsolicited message error.