OC_SetScanTime Library of Routines 6–73
Publication 1747-6.5.3 June 1998
OC_SetScanTime OC_SetScanTime sets the I/O scan time and I/O scan interval of the scanner.
Syntax:
int OC_SetScanTime(HANDLE handle, int mode, int time);
Parameters:
Description:
A scan time change will take effect when the scanner transitions from Idle mode to Scan mode.
Return Value:
Considerations:
Supported in the DOS API library and the Windows NT API library
Example:
HANDLE Handle;
int retcode;
retcode = OC_SetScanTime( Handle, SCAN_PERIODIC, 20 );
/* Scan set to start every 5 msec. */
Parameter: Description:
handle
Must be a valid handle returned from OC_OpenScanner
mode
time
If mode is:
SCAN_PERIODIC time determines the frequency of I/O scans in
multiples of 250us and must contain a value
between 1 and 255.
SCAN_DELAYED time determines the delay between I/O scans in
multiples of 10us and must contain a value
between 1 and 256.
The default
mode is SCAN_PERIODIC and the default time is 10 if
OC_SetScanTime is not used to change the scan time.
Name: Value: Description:
SUCCESS
0
scan time was set successfully
ERR_OCACCESS
2
handle does not have access to the scanner
ERR_OCINIT
5
scanner has not been initialized, see OC_InitScanner
ERR_OCPARAM
8
parameter contains invalid value