Publication 1747-UM002A-US-P - June 2000
A-2 Error Codes
Extended Error Codes
The OC_GetExtendedError function returns error information in a
structure of type OCEXTERR. This structure is five bytes in length and
contains the following information:
When the scanner encounters an error, the extended error code and
associated slot (if any) is written to the extended error code and slot
number fields. Error-dependent information is written to the
remaining field and the scanner goes to Idle mode.
The extended error codes that can be reported by the scanner are:
Buffer Offset: Bytes: Description:
0 1 extended error code
1 1 associated slot or file number
2 3 error code data
Extended Error
Code:
Description:
0x00 No errors present
0x01 Downloaded directory file is invalid
0x08 Internal software error
0x12 Downloaded configuration is corrupted
0x21 Power fail on expansion rack occurred
0x2E Invalid DII input slot
0x40 Host Watchdog Timeout
0x50 Data error while accessing module
0x51 Stuck PINT error
0x52 Module is missing
0x53 Module detected in unused slot
0x54 Module type does not match downloaded configuration
0x55 Module I/O mix does not match downloaded
configuration
0x56 Rack type does not match downloaded configuration
0x57 Specialty I/O module lock memory command timeout
0x58 Specialty I/O module fault
0x59 Specialty I/O module command timeout
0x5A Module interrupt problem
0x5B G file configuration error
0x5C M0/M1 file configuration error
0x5D Unsupported interrupt service requested by module
0x5E I/O driver error