Publication 1747-UM002A-US-P - June 2000
Error Codes A-3
The error code data provides information specific to the cause of all
extended errors, except 0xF0. The first byte of the error code data
contains a subsystem identifier with the following information:
The second byte of the error code data provides details about the
subsystem identifier with the following information:
0x60 - 0x8F Module specific errors (see I/O module documentation)
0x90 MINT occurred on disabled slot
0x91 PINT occurred on disabled slot
0x93 Unsupported module error
0x94 Module has been inserted or reset
0xF0 Internal scanner error
Subsystem ID: Description:
0x06 Scanner Communications
0x08 Backplane Interface (module I/O)
Error Code: Description:
0x00 Download error - invalid directory file pointer block
0x01 Download error - change to Idle mode failed
0x02 Download error - configuration file CRC failed (byte 1
contains the file number)
0x03 Download error - directory CRC failed
0x04 Download error - input or output image exceeds partition
allocation (byte 1 contains 0 for output image, 1 for input)